Voltage transformer of this type epoxy resin cast fully insulated fully enclosed structure.
For the rated frequency of 50Hz-60Hz .Voltage 3,6,10kV and below the power system voltage.Energy measurment and relay protection .
TRANSDUCER | |
Load power factor | 0.8(lag) |
Surface creepage distance |
Class II |
Product standard | GB1207 |
Specification
Type | Rated voltage ratio | Accuracy class | Rated output | limit output | Reted insulating level |
JDZX9-3 | 3/√3/0.1/√3/0.1/3 | 0.2/6P ,0.5/6P , 1/6P | 15/50 , 30/50 , 50/50 | 400 | 3.6/25/40 |
JDZX9-6 | 6/√3/0.1/√3/0.1/3 | 0.2/6P ,0.5/6P , 1/6P | 15/50 , 30/50 , 50/50 | 7.2/30/60 | |
JDZX9-10 | 10/√3/0.1/√3/0.1/3 | 0.2/6P ,0.5/6P , 1/6P | 20/100 , 50/100 , 80/100 | 12/42/75 | |
JDZXF9-3 | 3/√3/0.1/√3/0.1/√3/0.1/3 | 0.2/0.2/6P, 0.2/0.5/6P, 0.5/0.5/6P | 15/15/50 , 15/20/50 , 30/30/50 | 3.6/25/40 | |
JDZXF9-6 | 6/√3/0.1/√3/0.1/√3/0.1/3 | 0.2/0.2/6P, 0.2/0.5/6P, 0.5/0.5/6P | 15/15/100 , 15/20/100 , 30/30/100 | 7.2/30/60 | |
JDZXF9-10 | 10/√3/0.1/√3/0.1/√3/0.1/3 | 0.2/0.2/6P, 0.2/0.5/6P, 0.5/0.5/6P | 20/20/100 , 20/30/100 , 30/30/100 | 12/42/75 | |
Dimensions
JDZX (F) 9-3 6 10 | ||