How to install current transformer?

Views : 1892
Update time : 2024-08-09 13:05:16
How to install current transformer?
  • 1. The construction should be carri out according to the drawings, the wiring should be correct, the numbers on both ends of the wires should be clearly mark, and the numbering range should meet the requirements of the regulations.

  • 2. The secondary circuit wires or cables should all use copper wires. The cross-section of the current transformer loop wire should not be less than 2.5mm2, and the cross-section of the voltage transformer loop wire should not be less than 1.5mm2.
  • 3. The first terminal block of the current transformer outlet should use special current terminals. The secondary winding not use by the current transformer should be short-circuit and ground at the terminal board.
  • 4. There should be no joints in the secondary circuit wires in panels and cabinets, and there should be no joints in the middle of control cables or wires. If joints are necessary, they should be transitionally connect through the terminal box of their length.
  • 5. Of course, the polarity of the current transformer cannot be reverse, and the phase sequence and phase difference should comply with the design and regulatory requirements. Due to the wiring of the transformer for differential protection, the current phasor diagram of both arms must be measure before being put into operation to check the wiring. correctness
  • 6. Since the arrangement of secondary circuit wires should be neat and beautiful, the connecting screws between the wires, electrical components and terminal strips must not have loose connections, and the distance between the wire binding handles and the clamping points should meet the requirements of the regulations.

 

Related News
Read More >>
Rogowski Coil and 330 mV Inductive Sensors for LV Feeder Monitoring Rogowski Coil and 330 mV Inductive Sensors for LV Feeder Monitoring
Nov .24.2026
Explore Rogowski coil and 330 mV inductive sensor applications at LV incomers, outgoing feeders and power quality monitoring points.
Outdoor Split-Core CT for Light Rail: HEYI’s Korean Railway Applications Outdoor Split-Core CT for Light Rail: HEYI’s Korean Railway Applications
Nov .20.2026
Explore how HEYI’s outdoor split-core CT supports AC feeder monitoring in Korean railway stations, outdoor cabinets and depots.
Where Can the HEYI CCT-24 CT Clamp Current Sensor Be Used? Where Can the HEYI CCT-24 CT Clamp Current Sensor Be Used?
Nov .19.2026
Explore HEYI CCT-24 for solar storage, building submetering, equipment monitoring and distributed power measurement.
A Beautiful Land, A Long-Term Vision for HEYI in Central Asia A Beautiful Land, A Long-Term Vision for HEYI in Central Asia
Nov .18.2026
Discover HEYI’s long-term vision for Central Asia and how HEYI current transformers, split-core CTs and electrical measurement solutions aim to build stronger recognition across the region.