Why does the PC casing of the HK current transformer crack

Views : 465
Update time : 2025-08-23 13:39:36

1.Opening

For electronics & electric components like current transformeror metering transformer which need use for a long time. The PC plastic casing not only serves as insulation protection but also has to withstand assembly, transportation and environmental stresses. Once cracks occur, it may cause water ingress, creepage, metering drift, and even power outages.

Therefore, this article will mainly introduces the structure of HK current transformer, the causes of problems and improvement methods toavoid the occurrence of cracks as much as possible.

 

2.Introduction to the product structure and design

The mainstream HK push-button open-close type current transformer is composed of a silicon steel core , 99.9% pure copper coils, red copper terminal blocks and springs from the inside out. The product is divided into a U-shaped part and an I-shaped part, which are connected by hinges and opened with closed by buttons. Among them, the I-shaped part is clamped and fixed by the iron core at the connection and the button by a spring. These structural key points determine that the casing will be subjected to relatively large assembly and elastic energy storage release stresses locally.

 

3. Scenarios where cracks may occur

Be under the blazing sun for quite a long time: after beingunder the sun for a long time, this PC materials will graduallybecome brittle.

Improper logistics transportation and storage: Shaking, bumping and stacking during transportation can trigger hidden or through cracks at the stress concentration points of the shell.

Long-term internal force compression of I-shaped part springs: The continuous external support of the spring will keep the I-shaped part in a local state of being "stretched apart" under force. Over time, this can cause cracks.

4. Case studies and cause analysis

You can see cases in the following images. The cracking is concentrated at the button and the connection points at the I shape part. These two points are not only the force transmission points for opening and closing but also there are hotspots for stress concentration.

                

Directly reason: When after Ultrasonic die casting, the "tensile strength" formed by interfacial bonding/interlocking is insufficient and cannot counteract the outward force of the spring for a long time, resulting in the gradual cracking of the shell.

 

5. The corrective way adopted by ASCT

Inaddition to the above the basic HK current transformer materials, we also taken some measures as the following.

Upgrade materials: Replace the PC with a material system that has higher adhesion/toughness and is friendly to ultrasonic welding to enhance the crack resistance of the interface.

Optimize Structure: Check the preload and clearance to avoid long-term "oversaturation" of the support force. Thicken/reinforce the periphery of the spring seat but keep the transition between thick and thin smooth to reduce the stress gradient.

For the transformers made of the above-mentioned PC materials, we have also obtained the following certifications.

 

6.Contact

If you want to know more information about current transformer, please contact us.

E-mail:bethy@heyiele.com  Telephone number: 86-13968747975

                                     

 

Related News
Read More >>
Rogowski Coil and 330 mV Inductive Sensors for LV Feeder Monitoring Rogowski Coil and 330 mV Inductive Sensors for LV Feeder Monitoring
Nov .24.2026
Explore Rogowski coil and 330 mV inductive sensor applications at LV incomers, outgoing feeders and power quality monitoring points.
Outdoor Split-Core CT for Light Rail: HEYI’s Korean Railway Applications Outdoor Split-Core CT for Light Rail: HEYI’s Korean Railway Applications
Nov .20.2026
Explore how HEYI’s outdoor split-core CT supports AC feeder monitoring in Korean railway stations, outdoor cabinets and depots.
Where Can the HEYI CCT-24 CT Clamp Current Sensor Be Used? Where Can the HEYI CCT-24 CT Clamp Current Sensor Be Used?
Nov .19.2026
Explore HEYI CCT-24 for solar storage, building submetering, equipment monitoring and distributed power measurement.
A Beautiful Land, A Long-Term Vision for HEYI in Central Asia A Beautiful Land, A Long-Term Vision for HEYI in Central Asia
Nov .18.2026
Discover HEYI’s long-term vision for Central Asia and how HEYI current transformers, split-core CTs and electrical measurement solutions aim to build stronger recognition across the region.