range of current transformers are combination designed 3 CT in 1, save more space comparing general unit CT, suitable for primary current 60A to 200A,
supporting the use of molded case circuit breaker according to the rated current size.
Electrical Parameter | Mechanical Parameter | ||
Rated Frequency | 50/60Hz | Rated Test Voltage | 3KV AC (1 MIN) |
Rated Input | 75A-600A | Place of installation | Indoor |
short-time thermal current (lth) | 60lh | Class | 0.5,0.2,0.5S,0.2S |
Secondary | 5A , 1A | Aititude | <1000m |
Humidity | <80% | Ambient temperature | -5℃~40℃ |
Operating temperature | -10℃~85℃ | Housing self-extingshing class | VO |
Specification
Model | Ratio (A) | Rated power(VA) | Cable Dimension(mm) | voltage(V) | Frequency(HZ) |
D-363 | 50/5A | 1.5 | 3*30mm | 720 | 50/60 |
75/5A | 1.5 | 3*30mm | 720 | 50/60 | |
100/5A | 1.5 | 3*30mm | 720 | 50/60 | |
150/5A | 2.5 | 3*30mm | 720 | 50/60 | |
200/5A | 3.75 | 3*30mm | 720 | 50/60 | |
250/5A | 5 | 3*30mm | 720 | 50/60 | |
300/5A | 5 | 3*30mm | 720 | 50/60 | |
400/5A | 5 | 3*30mm | 720 | 50/60 | |
500/5A | 5 | 3*30mm | 720 | 50/60 |
Model | Ratio (A) | Rated power(VA) | Cable Dimension(mm) | voltage(V) | Frequency(HZ) |
D-364 | 300/5A | 1.5 | 3*40mm | 720 | 50/60 |
400/5A | 1.5 | 3*40mm | 720 | 50/60 | |
500/5A | 1.5 | 3*40mm | 720 | 50/60 | |
600/5A | 2.5 | 3*40mm | 720 | 50/60 |
Dimensions
D363 |
D364 |
Accuracy test
You can get a beautiful gift by interacting with us in the following ways
HEYI © All Rights Reserved.