Smart Circuit Breaker HY-R0 Series :
The R0 series circuit breakers stand out as a versatile solution, catering to users or loads with an AC frequency of 50/60Hz, a rated operating voltage of 230/400V, and a rated operating current of 63A and below. Beyond the fundamental attributes of traditional circuit breakers, the R0 series introduces a host of advanced features, combining electronic protection measures (over/under voltage, overcurrent, overload, leakage, etc.) with the convenience of remote control.
Key Technical Specifications:
AC Frequency: 50/60Hz
Rated Operating Voltage: 230/400V
Rated Operating Current: Up to 63A
Technical Data
Project | Parameter | |
Electrical parameters | Rated operating voltage | AC 230V/400V |
Frame rated current | 63A | |
Breaking capacity | 1cs: 6000A | |
Rated current | 16A/25A/32A/40A/50A/63A | |
Accuracy level | No metering | |
Power consumption | Standby power consumption: ≤5W | |
Trip power consumption: ≤15W | ||
Closing power consumption: ≤15W | ||
Minimum operating voltage | ≧ 70VAC | |
Communication | Communication interface | 485 |
Communication protocol | Modbus-RTU (optional) | |
Operating environmental conditions |
Operating temperature | -25℃~+ 70℃ |
Pollution degree | Level 2 | |
Installation | Wiring | Adopts clamp terminal (wire cross-sectional area up to 35 square millimeters) |
Guide rail | Installed on 35.5×7.5mm standard rail | |
Service life | Mechanical life | ≥5 years |
Electrical life | ≥5 years |
Dimension |