Residual current device sensor (RCDs) or residual current sensors are indispensable safety components used to protect against electrical and ground faults in a variety of applications. Their high sensitivity, fast tripping mechanisms and compatibility with a variety of electrical systems make them vital for ensuring electrical safety in residential and industrial environments and preventing accidents and damage.
Standards and Regulations:
Residual current device sensor are subject to various national and international standards and regulations that define their installation requirements and performance standards. HYCA-F03 complies with IEC62752, IEC62955, UL2231 standards.
Model | Corresponding standards | DC trigger threshold | AC trigger threshold |
HYCA-03/PD | IEC62752 | 6mA | 30mA |
Electrical/Reliability Characteristics | |
Working Temperature | -40℃~85℃ |
Storage Temparature | -20℃~65℃ |
Supply Voltage(VDD) | 4.85~5.15 VDC recommend 4.9-5.1 VDC |
Static Power Consumption | 110mW |
Clearance (Primary-Primary/Secondary) |
≥6.5mm ≥10mm |
Creepage Primary-Primary/Secondary) |
≥8mm ≥10mm |
Voltage Input, low level | 0~0.6VDC |
Voltage Input, high level | 4.2~5VDC |
Designed Life | ≥20 years |
Working Altitude | ≤4000m |
Trip-Current (residual current related characteristics. | |||||
Wav. | Freq. | Min. | Typ | Max. | Unit |
AC | 50Hz | 20.0 | 23.0 | 26.0 | mA |
A0° | 50Hz | 11.0 | 15.0 | 30.0 | mA |
A90° | 50Hz | 10.0 | 20.0 | 30.0 | mA |
A135° | 50Hz | 10.0 | 24.0 | 35.0 | mA |
2PDC | 50Hz | 3.5 | 5.0 | 7.0 | mA |
3PDC | 50Hz | 3.1 | 4.6 | 6.2 | mA |
S-DC | – | 3.0 | 4.6 | 6.0 | mA |
Trip-Time (residual current related characteristics | ||||
Wav. | Freq. | Current | TYP. | Unit |
AC | 50Hz | 30mA | 25 | ms |
AC | 50Hz | 60mA | 16 | ms |
AC | 50Hz | 150mA | 15 | ms |
AC | 50Hz | 5A~100A | 8.5 | ms |
A0° | 50Hz | 42mA | 25 | ms |
A0° | 50Hz | 84mA | 18 | ms |
A0° | 50Hz | 210mA | 10 | ms |
A0° | 50Hz | 42mA+6mADC | 18 | ms |
A0° | 50Hz | 84mA+6mADC | 15 | ms |
A0° | 50Hz | 210mA+6mADC | 15 | ms |
S-DC | 6mA | 48 | ms | |
S-DC | 60mA | 16 | ms | |
S-DC | 300mA | 8.5 | ms | |
2PDC/3PDC | 50Hz | 60mA | 20 | ms |
2PDC/3PDC | 50Hz | 120mA | 25 | ms |
2PDC/3PDC | 50Hz | 300mA | 12 | ms |
2PDC/3PDC | 50Hz | 5~50A | 12 | ms |
Dimensions
Mechanical dimension(for reference only) |
Standards
IEC62752
IEC62955
UL2231