The product is equipped with a metal exander,fully sealed structure ,the primary winding as a "U" shaped capacitor-type insulating structure,dielectric loss rate is small low partial discharge .The secondary winding is generally 4-6windings can be any combination of levels ,according to the accurate level of user need to producte the measured level of 0.2S class of special purpose current transformer.
The current transformer for outdoor installations LB7-220 applies to an altitude of 1700 m the following areas ,LB7-220W1 apply to the dirty areas below an altitudeof 1700 m .Environment al temperature -30°C-40°C.
Rated current ratio | Class combination | Accuracy class | Rated output | Accuracy limit factor | |
Full turn number | Tap | ||||
2*600/5, (2*300/5), 2*750/5, (2*400/5), 2*800/5, (2*400/5), 2*1000/5, (2*500/5), 2*1200/5, (2*600/5), 2*1250/5, (2*750/5) |
P1/P2/0.5(0.2), P1/P2/P1/P1/0.5(0.2), P1/P2/P1/P1/P1/0.5/(0.2), P1/P2/P1/0.5/0.2, P1/P2/P1/0.5/0.2S, P1/P2/P1/P1/P1/0.2S |
5P,10P | 50 | 20 | |
5P,10P | 50 | 25 | |||
50 | 12.5 | ||||
0.5 | 50 | 40 | |||
0.2 | 50 | 40 (0.5class) | |||
0.2S | 50 | 40 (0.5class) | |||
Rated current ratio | Rated short time thermal current | Rated dynamic current | Rated insulation level | Porcelanin creepage distance | oil weight Total weight |
2*600/5, (2*300/5), 2*750/5, (2*400/5), 2*800/5, (2*400/5), 2*1000/5, (2*500/5), 2*1200/5, (2*600/5), 2*1250/5, (2*750/5) |
(5s) 21-42 or (3s) 31.5-63 | 55-110 or 80-160 | 252/395/950 | 410 | 365/1300 |
550 | |||||
630 | |||||
Dimensions
Number | Name | Outline Dimensions |
1 | Valve | |
2 | Earth stud | |
4 | Junction box | |
5 | Oil tank | |
6 | Procelain bushing | |
7 | Oil conserivator | |
8 | Primary outlet terminal | |
9 | Connecting sheet | |
10 | Oil level observation window | |
11 | Expander | |
12 | Overvoltage protection |
Accuracy test